湖南电力 ›› 2022, Vol. 42 ›› Issue (4): 18-22.doi: 10.3969/j.issn.1008-0198.2022.04.004

• 特别推荐 • 上一篇    下一篇

基于声信号和一维卷积神经网络的绝缘子污秽度监测方法研究

李振华1, 李浩1, 黄景光1, 张磊1, 吴琳2   

  1. 1.三峡大学,湖北 宜昌 443002;
    2.国网湖北省电力有限公司技术培训中心,湖北 武汉 430014
  • 收稿日期:2022-07-05 出版日期:2022-08-25 发布日期:2022-10-14
  • 作者简介:李振华(1986),男,博士,教授,主要从事电力设备状态监测、电磁兼容方面的研究。
  • 基金资助:
    国家自然科学基金项目(51877122);强电磁工程与新技术国家重点实验室开放课题(2022KF005)

Insulator Pollution Monitoring Based on Acoustic Signal and One-Dimensional Convolutional Neural Network

LI Zhenhua1, LI Hao1, HUANG Jingguang1, ZHANG Lei1, WU Lin2   

  1. 1. China Three Gorges University,Yichang 443002,China;
    2. State Grid Hubei Electric Power Company Limited Technology Training Center,Wuhan 430014,China
  • Received:2022-07-05 Online:2022-08-25 Published:2022-10-14

摘要: 针对高压输电线路污秽绝缘子放电模式监测,设计一种新型的一维卷积神经网络结构(1D-CNN),提出一种基于声发射信号和1D-CNN的污秽绝缘子放电模式监测方法。将实验室采集到的不同放电状态下的声发射信号经过预处理后,利用卷积神经网络对放电信号样本进行自适应特征提取和特征降维,以减少训练模型参数和计算量,最终使用Softmax函数对预测结果进行分类。识别结果表明模型能够达到99.84%以上的识别率,减少了传统绝缘子污秽度监测方法中人工对数据进行预处理的过程,可有效应用于污秽绝缘子放电模式监测任务。

关键词: 污秽绝缘子放电, 卷积神经网络, 声发射信号, 故障诊断, 深度学习

Abstract: Aiming at the problem of discharge mode monitoring of polluted insulators in high voltage transmission lines,a new one-dimensional convolutional neural network structure (1D-CNN) is designed for monitoring the discharge patterns of fouled insulators in high-voltage lines, and a fouled insulator discharge pattern monitoring method based on acoustic emission signals and 1D-CNN is proposed. After preprocessing the acoustic emission signals collected in the laboratory under different discharge states, the convolutional neural network is used to perform adaptive feature extraction and feature dimensionality reduction on the discharge signal samples to reduce the training model parameters and computation, and finally the Softmax function is used to classify the prediction results. The recognition results show that the model can achieve a recognition rate of more than 99.84%, which effectively solves the process of manual preprocessing of data in the traditional insulator fouling degree monitoring method and can be effectively applied to the task of fouling insulator discharge pattern monitoring.

Key words: discharge of polluted insulator, convolutional neural network, acoustic emission signal, fault diagnosis, deep learning

中图分类号: