湖南电力 ›› 2024, Vol. 44 ›› Issue (5): 9-16.doi: 10.3969/j.issn.1008-0198.2024.05.002

• 特约专栏:电力防灾减灾 • 上一篇    下一篇

非制冷红外探测器在山火探测应用的影响分析

欧阳亿1, 张华玉1, 吴雯丽2, 沈佳彬2   

  1. 1.电网防灾减灾全国重点实验室(国网湖南省电力有限公司防灾减灾中心),湖南 长沙 410129;
    2.国科大杭州高等研究院,浙江 杭州 310024
  • 收稿日期:2024-08-05 修回日期:2024-08-11 出版日期:2024-10-25 发布日期:2024-11-06
  • 作者简介:欧阳亿(1996),男,工程师,主要从事电网防灾减灾技术研究工作。
  • 基金资助:
    国家电网有限公司科技项目(5200-202123097A-0-0-00)

Analysis of the Impact of Uncooled Infrared Detectors in Wildfire Detection Applications

OUYANG Yi1, ZHANG Huayu1, WU Wenli2, SHEN Jiabin2   

  1. 1. State Key Laboratory of Disaster Prevention & Reduction for Power Grid (State Grid Hunan Electric Power Company Disaster Prevention and Reduction Center) ,Changsha 410129, China;
    2. Hangzhou Institute for Advanced Study UCAS,Hangzhou 310024,China
  • Received:2024-08-05 Revised:2024-08-11 Online:2024-10-25 Published:2024-11-06

摘要: 针对现有研究未对星载红外非制冷探火能力和空间可靠性定量化分析,限制山火监测卫星发展的问题,利用红外遥感成像原理,通过理论推导和地面燃烧实验,系统对比星载红外非制冷和制冷的探火能力,同时分析非制冷空间可靠性。结果表明:在黑体辐射中,非制冷和制冷红外可探测473 K面积像素比不小于1/9亚像素目标;在真实燃烧物中,两者均可探测面积像素比1/36亚像素山火目标,其中木材信杂比最小,为14 dB;对于500 km、60 m分辨率的山火小卫星,星载红外非制冷可探测10 m级小面积山火。同时空间热实验结果表明:星上控温在1℃以内,非制冷可保持良好的空间可靠性,为构建低轨山火红外卫星星座提供科学指导,提高输电线路山火时空精度,保障电网稳定安全运行。

关键词: 非制冷红外, 信杂比, 山火探测, 电网

Abstract: In response to the lack of quantitative analysis on the fire detection capability and spatial reliabil‍ity of spaceborne infrareduncooled systems in existing research, which limits the development of wildfire monitoring satellites, the infrared remote sensing imaging principle is utilized to systematically compare the fire detection capabilities of spaceborne infrared non cooling and cooling systems through theoretical derivation and ground combustion experiments, while analyzing the reliability of uncooledspace.The results indicate that both uncooled and cooled infrared detectors can detect sub-pixel targets with a temperature of 473 K occupying at least 1/9 of a pixel in blackbody radiation. In the case of real burning materials, both types can detect wildfire targets that occupy 1/36 of a pixel, with the minimum signal‍‍‍-to-clutter ratiofor wood being 14dB.For a small wildfire satellite operating at an altitude of 500 km with a resolution of 60 meters, the spaceborne uncooled infrared detector is capable of detecting small area wildfires on the order of 10 meters.Additionally, results from spatial thermal experiments demonstrate that maintaining temperature control within 1 ℃ on orbit allows uncooled detectors to maintain good spatial reliability. This provides valuable scientific guidance for constructing low earth orbit infrared satellite constellations for wildfire detection, ultimately improving the spatiotemporal accuracy of monitoring wildfires along transmis‍sion lines and ensuring the stable and safe operation of the power grid.

Key words: uncooled infrared, signal-to-clutter ratio (SCR), wildfire detection, power grid