摘要: 特高压输电线路电晕损失研究对合理控制线路损耗和提升线路环保水平具有重要意义。在此背景下,采用模拟试验和理论计算相结合的技术路线,基于电晕笼试验装置研究特高压输电线路电晕损失等效测量方法,实测和等效测量结果的对比验证了单导线和1 000 kV特高压试验线路采用等效测量方法得出的干燥和淋雨条件下电晕损失值的准确性,证明了基于电晕笼进行特高压输电线路电晕损失等效测量的良好效果。

关键词: 电晕损失, 电晕笼, 特高压, 分裂导线, 等效测量

Abstract: Research on corona loss in UHV transmission lines holds significant implications for rational control of line losses and enhancement of environmental protection level. In this context, the technical route integrating simulation experiments and theoretical calculations is adopted to study the equivalent measurement method of corona loss of UHV transmission lines based on corona cage test device. Comparative analyses between actual sample measurements and equivalent test results validate the accuracy of corona loss values derived from equivalent methods under both dry and rain-wetting conditions for single conductor and 1 000 kV UHV AC test lines. The findings conclusively demonstrate the validity of corona cage-based equivalent measurement approaches for UHV transmission line corona loss assessment.

Key words: corona loss, corona cage, ultra-high voltage(UHV), bundled conductor, equivalent measurement