湖南电力 ›› 2026, Vol. 46 ›› Issue (3): 53-60.doi: 10.3969/j.issn.1008-0198.2026.03.007

• 电网运行与控制 • 上一篇    下一篇

基于潮流计算的台区低电压成因量化分析

段绪金, 王小源, 莫文慧, 唐海国, 朱吉然   

  1. 国网湖南省电力有限公司电力科学研究院,湖南 长沙 410208
  • 收稿日期:2025-11-07 修回日期:2026-04-27 出版日期:2026-06-25 发布日期:2026-07-07
  • 作者简介:段绪金(1989),男,高级工程师,主要研究方向为分布式能源接入、低电压治理、电缆诊断技术等。
  • 基金资助:
    国网湖南省电力有限公司科技项目(5216A321N302)

Research on Quantitative Analysis of Low Voltage Causes in Distribution Areas Based on Power Flow Cal‍culation

DUAN Xujin, WANG Xiaoyuan, MO Wenhui, TANG Haiguo, ZHU Jiran   

  1. State Grid Hunan Electric Power Company limited Research Institute, Changsha 410208, China
  • Received:2025-11-07 Revised:2026-04-27 Online:2026-06-25 Published:2026-07-07

摘要: 针对配电台区低电压成因多、耦合性强、治理决策缺乏定量依据的问题,提出一种基于三相四线制潮流计算的低电压成因量化分析方法。该方法在考虑负荷不平衡及中性线、接地回路影响的基础上,构建台区精细化模型,采用前推回代法计算节点电压分布,并提出低电压指数作为综合评价指标。通过变参量分析,对变压器容量与挡位、线路线径、无功补偿及三相负荷不平衡等因素进行单变量扰动计算,实现低电压成因的定量评估与主因识别。算例结果表明,该方法能够有效刻画台区低电压特征,区分不同治理因素的影响程度,为低电压精准治理提供定量决策依据。

关键词: 低电压治理, 潮流计算, 三相四线制, 量化分析, 台区仿真

Abstract: To address the issues of multiple causes, strong coupling, and lack of quantitative basis in decision-making for low-voltage problems in distribution feeders, a quantitative analysis method for low-voltage causes based on three-phase four-wire load flow calculation is proposed. The method constructs a detailed feeder model considering load unbalance, neutral conductor, and grounding loop effects, and calculates the nodal voltage distribution using the forward-backward sweep method. A low-voltage index is introduced as a comprehensive evaluation metric. Through parametric analysis, single-variable perturbation calculations are performed on transformer capacity and tap settings, line conductor sizes, reactive power compensation, and three-phase load unbalance to achieve quantitative assessment and identification of the primary causes of low voltage. Case study results indicate that the proposed method can effectively characterize low-voltage features of the feeder, distinguish the influence degree of different mitigation factors, and provide a quantitative decision-making basis for precise low-voltage control.

Key words: low-voltage governance, power flow calculation, three-phase four-wire system, quantitative analysis, distribution station area simulation

中图分类号: