Hunan Electric Power ›› 2022, Vol. 42 ›› Issue (3): 49-54.doi: 10.3969/j.issn.1008-0198.2022.03.009

• Researches and Tests • Previous Articles     Next Articles

Research on Distributed Photovoltaic Grid Connection Modeling Based on RTDS

XU Biao1, LONG Xuemei2, YAN Yabing2, DING Yu2, OUYANG Zongshuai2   

  1. 1. State Grid Hunan Electric Power Company Limited, Changsha 410004, China;
    2. State Grid Hunan Electric Power Company Limited Research Institute, Changsha 410007, China
  • Received:2022-01-10 Revised:2022-01-20 Online:2022-06-25 Published:2025-08-05

Abstract: With the large-scale development of distributed photovoltaic, it is necessary to strengthen the modeling research of distributed photovoltaic grid connection. Firstly, based on RTDS real-time simulation platform, photovoltaic grid connected models such as photovoltaic array, grid connected inverter, filter and isolation transformer are established. Secondly, when the power grid is three-phase symmetrical, the double loop control structure is used to build the photovoltaic control system model. Then, considering the asymmetric fault of power grid, a photovoltaic negative sequence control model based on double synchronous rotating coordinate system is established. Finally, the simulation results show that the proposed model also has good performance in case of power grid failure, and it is verified that photovoltaic negative sequence control can effectively reduce negative sequence current and current distortion.

Key words: distributed photovoltaic, RTDS, asymmetric fault, negative sequence control