Hunan Electric Power ›› 2023, Vol. 43 ›› Issue (6): 76-81.doi: 10.3969/j.issn.1008-0198.2023.06.012

• New technology and Application • Previous Articles     Next Articles

Application of Improved Morphological Filtering in Voltage Sag Detection Algorithm

ZENG Jinhui1, HUANG Mingxuan1, ZOU Bin1, HUANG Xi2, NING Zhihao3   

  1. 1. School of Electrical and Information Engineening,Hunan University of Technology,Zhuzhou 412007,China;
    2. State Grid Huaihua Power Supply Company,Huaihua 418000,China;
    3. State Grid Hunan Electric Power Company Limited Research Institute,Changsha 410208,China
  • Received:2023-08-02 Revised:2023-09-22 Online:2023-12-25 Published:2024-01-07

Abstract: On the basis of traditional dq transform detection method, a voltage sag detection algorithm based on morphological filtering is proposed. This algorithm improves the problems of low real-time performance and insufficient accuracy of ordinary low-pass filters, and can also filter out the second harmonic component generated by coordinate transformation in traditional detection methods to quickly extract voltage sag features. Finally, a model is built on a simulation platform to verify the real-time and stability of the algorithm.

Key words: voltage sag, detection algorithm, dq transformation, morphological filtering

CLC Number: