Hunan Electric Power ›› 2023, Vol. 43 ›› Issue (6): 99-105.doi: 10.3969/j.issn.1008-0198.2023.06.015

• New technology and Application • Previous Articles     Next Articles

Parameter Design and Power Flow Regulation Application for High-Voltage Phase Shifting Transformer

XU Shunkai, ZHU Jiran, TANG Haiguo, ZHAO Miao, ZHANG Di, DENG Wei   

  1. State Grid Electric Power Company Limited Research Institute, Changsha 410208,China
  • Received:2023-07-09 Revised:2023-08-22 Online:2023-12-25 Published:2024-01-07

Abstract: For the transmission efficiency of some lines is insufficient under the natural distribution of power flow, this article provides a detailed analysis of the topology and working principle of the high-voltage phase shifting transformer, deduces its equivalent model, and conducts in-depth research on its power flow regulation theory and power improvement effect in a dual ended power supply system. The simulation results show that the active power flow regulation range at the end of the line is 90.19~1 524 MW. Finally, an equal proportion prototype is developed and a dual terminal power supply experimental platform is built for testing. The adjustment range of the experimental prototype for the active power at the end of the line was 24.86~214.83 W, which verifies the effectiveness and feasibility of the device.

Key words: high-voltage phase shifting transformer, power flow regulation, transmission capacity, equivalent model, parameter design, prototype development