Hunan Electric Power ›› 2026, Vol. 46 ›› Issue (3): 139-145.doi: 10.3969/j.issn.1008-0198.2026.03.018

• Electric Power Prevention and Reductione • Previous Articles     Next Articles

Explosion-Proof Test Scheme for UHV Flexible DC Converter Valve Submodules

LI Qi1, YANG Yong1, ZHANG Tao1, ZHOU Huiying2, SITU Liukai2, QIN Liang2   

  1. 1. State Grid Economic and Technological Research Institute Co., Ltd., Beijing 102209, China;
    2. School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China
  • Received:2026-02-03 Revised:2026-03-24 Online:2026-06-25 Published:2026-07-07

Abstract: The explosion-proof test for submodules of UHV flexible DC transmission converter valves suffers from inadequate charging voltage, incomplete test coverage, and ambiguous criteria. This paper examines typical explosion faults in UHV flexible DC converter valve submodules, identifies key weak points under explosive loads, and defines quantified test indicators centered on these vulnerabilities. A repeatable explosion-proof test scheme is then designed for submodules, including tests for upper/lower arm through-faults, bypass switch failure, and post-fault current-carrying capability. Finally, prototype submodules from a domestic UHV flexible DC project undergo explosion-proof testing, confirming their compliance with explosion-resistance requirements.

Key words: UHV flexible DC, converter valve, submodule explosion-proof, explosion characteristics, explosion-proof test

CLC Number: