Hunan Electric Power ›› 2026, Vol. 46 ›› Issue (5): 16-23.doi: 10.3969/j.issn.1008-0198.2026.05.003

• Source?Grid Coordination and Energy Conversion and Utilization • Previous Articles     Next Articles

Analysis of Voltage and Frequency Characteristics of Small Hydropower Islanded Grid Considering Governor and Excitation Regulation Characteristics

TAN Liming1, OUYANG Fan1, LI Zhenwen2, LIU Yonggang2, XIAO Fan3, OUYANG Zongshuai1   

  1. 1. State Grid Hunan Electrical Power Company Limited Research Institute, Changsha 410208, China;
    2. State Grid Hunan Electrical Power Company Limited, Changsha 410004, China;
    3. Wuhan University of Technology, Wuhan 430070, China
  • Received:2026-06-23 Revised:2026-07-19 Published:2026-11-06

Abstract: Existing studies mostly treat voltage and frequency as decoupled independent variables, neglecting the voltage-frequency coupling effect caused by constant-impedance loads and frequency-dependent synchronous reactance. This paper establishes a coupled voltage-frequency steady-state analytical model considering governor droop characteristics and excitation saturation constraints, derives simultaneous voltage-frequency equations for the islanded grid, and reveals the impact mechanism of excitation saturation on steady-state operating points. A simulation model of a 10 kV neutral ungrounded distribution network incorporating small hydroelectric generating units is established, and the correctness of the coupled model has been verified under load levels ranging from 50% to 150%. Simulation results show that the excitation system rapidly saturates at its ceiling after islanding, fully exposing the voltage-frequency coupling effect. The voltage-dependent characteristic of constant-impedance loads cannot compensate for the power deficit exceeding unit capacity under heavy-load operating conditions.

Key words: small hydropower, islanded grid, voltage-frequency coupling, governor, excitation regulation, steady-state analytical model