Hunan Electric Power ›› 2024, Vol. 44 ›› Issue (3): 120-125.doi: 10.3969/j.issn.1008-0198.2024.03.017

• New Technology and Application • Previous Articles     Next Articles

Seismic Performance Simulation Analysis and Optimization Design of Tank Circuit Breaker

CHEN Yu1, GAO Yang2, SHEN Fenghui2, XU Meng1, LIU Yuntong2   

  1. 1. Liaoning High Voltage Electrical Products Quality Testing Co.,Ltd.,Shenyang 110025,China;
    2. New Northeast Electric Group High Voltage Switchgear Co.,Ltd.,Shenyang 110025,China
  • Received:2024-03-13 Revised:2024-04-16 Online:2024-06-25 Published:2024-07-10

Abstract: :Taking a 363 kV tank circuit breaker as the research object, the three-dimensional solid model is built according to the design drawings, and the seismic response spectrum with the seismic level of AG5 is applied to the model by using Ansys Workbench software for finite element analysis, and the simulation results under the combined condition of seismic loads are obtained. The structure is optimized and the seismic performance before and after optimization is compared and analyzed. The results show that the optimized tank circuit breaker can meet the seismic performance requirements of AG5 level, strengthening the support is beneficial to increase the natural frequency of the tank circuit breaker structure. After structural optimization, the stress level of the main components is reduced, and the maximum displacement response of the top of the bushing decreases from 90.072mm to 66.342 mm, which is more favorable to long-term safe and stable operation of tank circuit breaker equipment.

Key words: tank circuit breaker, seismic performance, finite element calculation, response spectrum, structural optimization

CLC Number: