Hunan Electric Power ›› 2025, Vol. 45 ›› Issue (4): 27-31.doi: 10.3969/j.issn.1008-0198.2025.04.005

• Expert Column:Electric Power Prevention and Reduction • Previous Articles     Next Articles

Study on Snow Flash Characteristics Under Horizontal Arrangement of DC Composite Bushing

WAN Xiaodong, YAO Tao, LI Jin, JIA Ru, CAI Lin   

  1. State Key Laboratory of Power Grid Environmental Protection (China Electric Power Research Institute), Wuhan 430074, China
  • Received:2025-06-04 Revised:2025-07-08 Online:2025-08-25 Published:2025-09-05

Abstract: After the DC composite through-wall bushing in the converter station is covered with snow, flashover may occur, causing power outages. This article presents a horizontal arrangement of contaminated composite hollow bushing in a large artificial climate laboratory, and conducts snow-covering flashover tests under direct current voltage. The results show that 50% withstand voltoage (U50) obtained by using a non-charged snow melting pressurization method is about 6.8% lower than U50 obtained by using a charged snow melting pressurization method. The U50 under the DC voltage of the snow-covered bushing decreases with the increase of salt density, but its characteristic index α is lower than the index obtained from the pollution test. When the salt density is 0.1mg/cm2, the U50 gradient under the horizontal arrangement of the snow-covering composite bushing is close to that under weak hydrophobicity of the contaminated bushing.

Key words: composite through-wall bushing, artificial snow-covering, salt density, DC voltage, flashover characteristics