Abstract: Based on the winding structure characteristics of an 18 phase wind power generation system, the fault conditions of a multi-phase wind turbine are analyzed. The faults that may occur in the multi-phase motor system can be directly regarded as open circuit faults, equivalent to the phase loss operation of the motor. By analyzing the mechanism of energy transmission on the grid side and the machine side, the reference value of the output current of the three-phase uncontrolled rectifier after winding open circuit and converter module fault in the system has been readjusted, and corresponding fault-tolerant control methods have been proposed. Finally, the effectiveness of the current redistribution control strategy for converter module faults and the DC short circuit fault control strategy is verified through simulation.

Key words: fault-tolerant control strategy, multi-phase wind turbine, phase loss fault, wind power generator fault